Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat

Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual .

Wallplate installation

  • Remove the wallplate from the thermostat, then follow the directions below for mounting.
  • Remove battery holder.
  • Pull here to remove the wallplate from new thermostat.
  • Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual .1Pull wires through wire hole.
  • Position wallplate on wall, level and mark hole positions with pencil.
  • Drill holes at marked positions as shown below, then tap in supplied wall anchors.
  • Place wallplate over anchors, insert and tighten mounting screws.Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 2
Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 3

Power options

Wiring terminal designations

Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.

Conventional Terminals:

  • Rc 24VAC power from cooling transformer
  • R 24VAC power from heatingm transformer
  • W Heat relay (stage 1)
  • W2 Heat relay (stage 2)
  • Y Compressor contactor (stage 1)
  • Y2 Compressor contactor (stage 2)
  • G Fan relay
  • C 24VAC common. For 2 transformer systems, use common wire from cooling transformer.Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 4

Heat Pump Terminals:

  • Rc 24VAC power from cooling transformer
  • R 24VAC power from heating transformer
  • O/B Changeover valve
  • Y Compressor contactor
  • Y2 Compressor contactor (stage 2) -TH5320U only
  • G Fan relay
  • Aux/E Auxiliary/Emergency heat relay
  • L Sends output when set to Em. Heat
  • C 24VAC commonHoneywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 5

Wiring conventional systems
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted

  • 1H/1C System (1 transformer)
  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • Y Compressor contactor
  • C 24VAC common [3]
  • W Heat relay
  • G Fan relay

Heat-only system

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • C 24VAC common [3]
  • W Heat relay

Heat-only System (Series 20) [5]

  • Rc [R+Rc joined by jumper]
  • R Series 20 valve terminal “R” [1]
  • Y Series 20 valve terminal “W”
  • C 24VAC common [3]
  • W Series 20 valve terminal “B”

Heat-only System (normally open zone valve) [5]

  • Rc [R+Rc joined by jumper]
  • R Power [1]
  • Y Normally open zone valve
  • C 24VAC common [3]

1H/1C System

  • (2 transformers)
  • Rc Power (cooling transformer) [1, 2]
  • R Power (heating transformer) [1, 2]
  • Y Compressor contactor
  • C 24VAC is common [3, 4]
  • W Heat relay
  • G Fan relay

Heat-only System with Fan

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • C 24VAC is common [3]
  • W Heat relay
  • G Fan relay

Cool-only System

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • Y Compressor contactor
  • C 24VAC common [3]
  • G Fan relay

2H/2C System (1 transformer) [6]

  • Rc Power [1]
  • R [R+Rc joined by jumper]
  • Y Compressor contactor (stage 1)
  • C 24VAC common [3]
  • W Heat relay (stage 1)
  • G Fan relay
  • W2 Heat relay (stage 2)
  • Y2 Compressor contactor (stage 2)

2H/2C System (2 transformers) [6]

  • Rc Power (cooling transformer) [1, 2]
  • R Power (heating transformer) [1, 2]
  • Y Compressor contactor (stage 1)
  • C 24VAC common [3, 4]
  • W Heat relay (stage 1)
  • G Fan relay
  • W2 Heat relay (stage 2)
  • Y2 Compressor contactor (stage 2)

Wire specifications:
Use 18- to 22-gauge thermostat wire A shielded cable is not required.

  •  Power supply. Provide disconnect means and overload protection as required.
  •  Remove jumper for 2-transformer systems.
  •  Optional 24VAC common connection.
  •  Common connection must come from cooling transformer.
  •  In Installer Setup, set system type to

Heat Only.

  •  In Installer Setup, set system type to 2Heat/2Cool Conventional.
  •  In Installer Setup, set changeover valve to O or B.
  •  In Installer Setup, set system type to 2Heat/1Cool Heat Pump.
  •  In Installer Setup, set system type to 2Heat/2Cool Heat Pump.
  •  In Installer Setup, set system type to 3Heat/2Cool Heat Pump.
  •  L terminal sends a continuous output when thermostat is set to Em. Heat. Connect to Honeywell zoning panels to switch the panel to Emergency Heat.

Wiring heat pump systems

Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 33

Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.

Thermostat mounting

  • Push excess wire back into the wall opening.
  • Plug wall opening with non-flammable insulation.
  • Align the 4 tabs on the wallplate with corresponding slots on the back of the thermostat.
  • Push gently until the thermostat snaps in place.Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 20

Installer setup

Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 21

Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired.

  •  To begin, press and hold the Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 22 and FAN buttons until the display changes.
  •  Press Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 23or t to change settings.
  •  Press NEXT to advance to next function.
  •  Press DONE to exit and save settings.
Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 24
Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 25

Setup function Settings & options (factory default in bold)

Special function

Auxiliary heat control (Setup Function 26):
Comfort Setting: The thermostat will prioritize comfort over economy depending on heat pump performance, load conditions and whether the thermostat is calling for the heat pump. Raising the temperature just a few degrees will often activate the auxiliary heat.
Economy Setting: The thermostat will attempt to reach the temperature setting without activating the auxiliary heat. The thermostat will wait to activate the auxiliary heat depending on heat pump performance, load conditions and how many degrees the temperature setting is changed.

Installer system test

  •  To begin, press and hold theHoneywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 27 and t buttons until the display changes.
  •  PressHoneywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 27to turn system on/off.
  •  Press NEXT to advance to next test
  •  Press DONE to terminate system test.Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 26
Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 29

System test System status

Specifications

Temperature Ranges

  • Heat: 40° to 90°F (4.5° to 32°C)
  • Cool: 50° to 99°F (10° to 37°C)

Operating Ambient Temperature

  • 32° to 120°F (0° to 48.9°C)

Shipping Temperature

  • -20° to 120°F (-28.9° to 48.9°C)

Operating Relative Humidity

  • 5% to 90% (non-condensing)

Physical Dimensions

  • TH5220D
  • 3-9/16” H x 5-13/16” W x 1-1/2” D
  • 91 mm H x 147 mm W x 38 mm D
  • TH5220D
  • 3-7/16” H x 4-1/2” W x 1-5/16” D
  • 86 mm H x 114 mm W x 33 mm D

Electrical Ratings

Customer assistance

For assistance with this product, please visit customer.honeywell.com Or call Honeywell Customer Care tollfree at 1-800-468-1502.

  • Pull at bottom to remove the thermostat from wallplate.Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 31
  • Turn the thermostat over to find model number and date code.Honeywell FocusPRO 5000 Series Non-Programmable Digital Thermostat Manual 32
CAUTION

EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.

ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.

MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal

Automation and Control Solutions

  • Honeywell International Inc.
  • 1985 Douglas Drive North
  • Golden Valley, MN 55422
  • Honeywell Ltd
  • 705 Montrichard Avenue
  • Saint-Jean-sur-Richelieu, Québec
  • J2X 5K8
  • customer.honeywell.com
  • ® U.S. Registered Trademark.
  • © 2013 Honeywell International Inc.
  • 69-2698EFS—03 M.S. Rev. 07-13 Printed in U.S.A

View Fullscreen

Read more: https://manuals.plus/honeywell/honeywell-focuspro-5000-series-non-programmable-digital-thermostat-manual#ixzz7edIFetif

Leave a comment

Your email address will not be published.